The GridBOSS spec sheet lists no DC input for panels. Its ports are for the utility, a generator, backed-up and non-backed-up loads, three hybrid inverters and four smart ports, and every one of them is rated 120/240 VAC. The panels' DC and the MPPT tracking are handled by the hybrid inverter, such as the FlexBOSS21 or 18kPV.

GridBOSS ratings (spec sheet v1.1.8)

EG4 calls GridBOSS a microgrid interconnect device (MID), a single point of connection for the utility, hybrid inverters, generators, smart loads and AC-coupled inverters.

ItemRating
Grid, backup and non-backup200 A each, 120/240 VAC
Hybrid inverter ports3, up to 90 A per port
Smart ports (AC coupling or load control)4, rated 125 A, 80 A, 60 A and 60 A
Generatorup to 125 A
Transfer timeabout 25 ms
Idle consumptionabout 55 W
Size and weight800 × 500 × 178 mm, 25 kg
Enclosure and warrantyNEMA 3R, 10 years

The spec sheet lists the EG4 12kPV, 18kPV, FlexBOSS18 and FlexBOSS21 as supported inverters and says third-party inverters are not supported and cannot be connected to the hybrid ports. The breaker sizes it gives for those ports are 50 A for the 12kPV, 70 A for the 18kPV and FlexBOSS18, and 90 A for the FlexBOSS21.

The panel-side numbers belong to the inverter

ItemFlexBOSS2118kPV
MPPTs33
Current per MPPT26 A, 26 A, 15 A (rated)25 A, 15 A, 15 A (max usable)
Short-circuit current per MPPT31 A, 31 A, 19 A31 A, 19 A, 19 A
Max DC input voltage600 V600 V
Recommended max solar array21 kW21 kW (18 kW max utilized)
Continuous AC output16 kW (12 kW on battery only)12 kW at 240 V
Battery voltage51.2 V48 V

Three FlexBOSS21 units at their 66.7 A maximum continuous output add up to about 200 A, the same as the GridBOSS backup-side limit. How to string the panels and which equipment can be paired are not something we judge; that follows each manufacturer's specifications.

Shopping for one? Browse home backup power stations →

Sources

  1. EG4 Electronics — GridBOSS
  2. EG4 Electronics — GridBOSS Spec Sheet (VERSION 1.1.8, 2026-06-17)
  3. EG4 Electronics — FlexBOSS21
  4. EG4 Electronics — FlexBOSS21 Spec Sheet (VERSION 1.3.0)
  5. EG4 Electronics — 18kPV
  6. EG4 Electronics — 18kPV Spec Sheet (VERSION 1.4.3)

We have not tested these products. Specs, prices, stock and terms are as published on these pages on the date above and can change; check the manufacturer or retailer before you buy.

More home batteries and backup guides

Home batteries and backupWhat Does a Solar-Plus-Battery Home Do From the Moment the Grid Fails Until Power Returns?Within seconds of losing grid power, a home PV system with battery storage can detect the outage and switch into an islanded mode that keeps the house…Read the guide →Home batteries and backupWhy Can't You Compare Home Battery Spec Sheets Line by Line?Capacity, continuous power, efficiency, and warranty are the lines that matter, yet each brand measures them under different conditions. Tesla lists…Read the guide →Home batteries and backupCan a Home Battery Start an Air Conditioner or a Well Pump?It depends on two power ratings, not on how many kWh are stored. One is continuous output, the other is how much current the battery can deliver for…Read the guide →Home batteries and backupIf the Power Goes Out at Night, How Many Hours Will a Home Battery Last?Runtime is the energy left when the outage starts divided by the load, and at night the energy left is mostly set by how much you told the battery to…Read the guide →Home batteries and backupWhat Limits a Home Battery and a Portable Generator During an Outage?A generator is limited by fuel and by where it can safely run; a battery is limited by its stored charge and by sunlight to refill it. DOE points out…Read the guide →Home batteries and backupCan Enphase IQ8 Microinverters Power a House in a Daytime Outage With No Battery?Enphase says that with IQ8 and IQ9 microinverters, "your lights, fans, and phones can stay powered even during a daytime grid outage, with or without…Read the guide →Home batteries and backupHow Much Rooftop Solar Can Connect Directly to a Tesla Powerwall 3?Up to 20 kW of solar (STC rating) per unit, across six MPPT inputs. Powerwall 3 has a solar inverter built in, and each unit delivers up to 11.5 kW of…Read the guide →Home batteries and backupCan You Install a Home Battery Without Solar Panels?It depends on the manufacturer. Tesla's Powerwall support page has a section titled "Without Solar" that describes charging from the grid when rates…Read the guide →Home batteries and backupHow Much Does a Home Battery Cost Once It Is Installed?EnergySage's quote data put a 13.5 kWh battery at about $15,650 before incentives, or $1,159 per kWh (updated August 26, 2026). The per-kWh price…Read the guide →Home batteries and backupDoes a Signature Solar "18kPV" Kit Come With 18 kW of Solar?No. "18kPV" is the model name of the EG4 inverter. Kit KIT-E0007 ships with eighteen 450 W or 460 W panels, which adds up to roughly 8.1 to 8.3 kW…Read the guide →Home batteries and backupDoes Adding a SolarEdge Home Battery Keep the Lights On in an Outage?Not on its own. SolarEdge says backup requires a connection to the Home Hub Inverter (single phase) and the Home Backup Interface, and that backup…Read the guide →Home batteries and backupDoes a Sol-Ark 15K's GEN Port Take a Generator or More Solar?Either one, but only one at a time. The 15K datasheet (PS-00001 Rev. 8) describes GEN as a bidirectional port for a fuel generator, AC-coupled PV or…Read the guide →Home batteries and backupWhat Do You Pay for a Base Power Battery If You Never Buy It?Base Power keeps ownership of the battery for the whole agreement. The homeowner pays an installation fee and, in Texas, a monthly membership, and…Read the guide →

All home batteries and backup guides · All guides and search